Size 0.923 x 2.10 inch; Mesh Opening Size 0.688 x 1.781 inch; 13 meshes per foot, 74 per cent open
area; Mesh Strand Width 0.106 inch; Mesh Strand Thickness 0.078 inch; Weight 0.75 pounds per square
foot. Provide manufacturer's attachment clips and use recommended fasteners to secure mesh to wall
The Holding Room should be contiguous with Security Operations Room and contain a shatterproof
observation window in the door. The door shall open outward. Door to holding room shall be Door Symbol
22, S-A, HW 10 (refer to VA Standard Details 08100-1, 08100-2 for door symbol and MCS 08700 for
hardware set). The holding room shall not have exterior windows.
//Provide one (1) each: motion detector, glass break module, and set of door contacts for holding room
door. Locate alarm system key pad on the entrance side of the holding room door. Connect the alarm
system for the holding room to the main building alarm system. Zone the alarm system so that the alarm
for the holding room can be set and disarmed independent of the main building alarm system.//
//