JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
7.8.6
FLOORING, LATEX MASTIC:
Traffic bearing, trowel applied, vinyl resin, neoprene resin, or polyacrylate resin flooring system, Latex
mastic (LM), complying with MCS 09701 shall be provided at locations listed in Schedule C. A reinforced
elastomeric waterproof membrane is not required for slab-on-grade installations.
Editing Note: Include following paragraph if central
computer room is required by program. Edit height of
floor system to match room size required.
//
7.8.7
COMPUTER ROOM FLOORING:
Provide a grid type computer access floor system in the computer room. For computer rooms 1,200
square feet and smaller, depress the floor slab a minimum of 12-inches; or provide access floor system
12-inches above the finished floor. For rooms with areas larger than 1,200 square feet, depress the floor
slab a minimum of 18-inches or provide access floor system 18-inches above the finished floor. Provide
ramp access at a maximum 1:12 slope for raised floor systems. //An access floor system constructed in
existing buildings should provide a minimum of 12 inches clear space.//
//
7.9 WALL COVERINGS:
Walls shall be covered in accordance with "Room Finish Schedule" in Schedule C, or other requirements
of this Solicitation. An estimate of base quantities of each type of wall covering that should be included in
the proposed rental rate is indicated on Exhibit A of Schedule B-1. Adjustments will be made at the end of
the project based on actual measurement and payment will be made per the pre-negotiated unit cost for
these items. Colors and patterns shall be as selected or approved by VA.
7.9.1
WALL TILE:
Ceramic wall tile shall be glazed tile. Tile materials and installation shall be in accordance with VA Master
Construction Specification 09310, Ceramic Tile. Ceramic tile at showers and wet locations shall be
installed over cement backer board or Portland cement mortar on metal lath.
7.9.2
WALL COVERINGS:
7.9.2.1 VINYL WALLCOVERING (W):
Vinyl wall covering shall comply with VA Master Construction Specification 09951, Vinyl Coated
Wallcovering. Provide Type II wall coverings with factory applied, clear, delustered poly-vinyl fluoride
coatings. Wall coverings shall be mildew and fungi resistant with Class A fire hazard classification.
7.9.2.2 WALLPAPER BORDERS:
Wallpaper borders shall be installed in spaces indicated in Schedule C. Borders shall be vinyl coated, 10-
inches in width as noted.
Editing Note: review extent of protective wall covering
(rigid PVC) and wall guards (bumper rails). Consider
types and severity of anticipated use by carts,
wheelchairs, mobile equipment, furniture, etc. in
decision on type of protection to be used.
Part I: Basic Solicitation Requirements Page 150 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages