connected to the Facility's external lightning protection system or directly run to earth ground on the
outside of the building by a mechanically and electrically protected #2 AWG stranded copper wire. Per
NEC, all grounding systems shall be bonded together.
//
6.7.6.3 TELECOMMUNICATIONS CLOSETS:
Provide these spaces as required by each System Design.
6.7.6.3.1 Remote or Secondary Telecommunications Closets
These types of closets shall be provided normally for special telecommunications systems that are allowed
in patient or other designated areas that exceed the 300 foot maximum conduit distance for the primary
telecommunications closets and the installation area is small enough as to not warrant the larger stacked
telecommunications closets. The use of these closets must be specifically approved by TCD-194D during
the design phase of the project. Each closet shall be a minimum of 5 ft. x 9 ft. or according to BICSI Wiring
Standards for the areas, the closet is to be installed, whichever is greater. Minimum door size shall be 36
inches wide by 84 inches high.
Each wall of the closet shall be provided floor to ceiling with fire retardant inch plywood wall covering.
6.7.6.3.2 Power & Lighting:
Emergency Power - Receptacles and lighting shall be on Emergency Power
120 VAC Receptacles Each telecommunications closet shall be provided with a separate 120 VAC 20
ampere circuit with two quadruplex receptacles, mounted in the center of each sideboard, 18 inches above
the floor.
120 VAC Receptacles Telecommunications backboards shall be provided with two (2) 120 VAC 20 Amp
quadruplex receptacles on the backboard with a minimum of two foot of separation and at 36 inches above
finished floor (one for special and the other for other signal equipment). Provide a separate AC circuit for
each six- (6) quadraplex receptacles.
Overhead Lighting - Install at least one (1) ceiling mounted two lamp 4 ft. fluorescent light fixture with an
"on-off" switch located on the inside wall.
6.7.7
POLICE AND ENGINEERING CONTROL ROOMS:
Provide these spaces as required by each system design.
6.7.8
SPECIAL REQUIREMENTS:
Editing Note: Coordinate with Schedule B.
6.7.8.1 NURSE CALL:
Provide Nurse Call System as specified in Schedule B.
Provide Emergency Nurse Call Stations in toilet areas only at the following locations:
//Dental Service (if not covered by a hands free telephone intercom system)//
//Drug Dependency Treatment Clinic//
//Oncology Clinic/Area (if not covered by a Nurse Call or Code One/Blue system)//
6.7.8.2 INTERCOMMUNICATION SYSTEM:
Provide intercommunication system in accordance with VA MCS 16760, Intercommunication System.
At loading docks, provide an empty conduit system for connection of a telephone intercom between the
Warehouse Office and loading dock where dock is not visible from the Receiving or Supervisor's office.