JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
//In the Dental Service, provide a dedicated intercom system throughout the Dental Suite. Refer to the
Schedule B for specific locations.//
//Provide appropriate systems at designated Facility ingress and egress points connected to the respective
Service Chief's Office or Security Service Control Room.//
//[Insert additional locations to suit project requirements.]//
6.7.8.3 RADIO ENTERTAINMENT SYSTEM:
Provide speakers for radio and entertainment program systems as follows:
All loudspeakers shall be of the recessed or ceiling type in lieu of surface-mounted type, wherever
possible.
Loudspeakers in Canteen//Dining Room// and //Retail Sales Areas// shall be operated by controls
located in Canteen Chief's Office.
Loudspeakers in each Waiting Room and other designated areas that contain PA speakers may be
combined within the same speaker back box and grille and use the same speaker cone as long as
each speaker function contains a separate matching transformer and voice coil for each service (i.e.,
one transformer and associated voice coil for RED and one transformer and associated voice coil for
PA).
Editing Note: Coordinate with Schedule B.
6.7.8.4 MASTER ANTENNA TELEVISION (MATV) SYSTEMS:
Master Antenna system shall be mounted on hinged poles (or equivalent) where subjected to salt-spray
atmosphere. Provide system as specified in Schedule B.
Editing Note: Edit to suit project requirements.
Coordinate with Schedule B.
6.7.8.5 MOTION INTRUSION DETECTION (MID):
Provide the systems identified in Paragraph 4.2.7 and Schedule B.
Editing Note: Edit to suit project requirements.
Coordinate with Schedule B.
6.7.8.6 CLOSED CIRCUIT TV SYSTEMS FOR DOOR MONITORING OR SECURITY:
Provide the systems identified in Paragraph 4.2.7 and Schedule B.
Editing Note: Coordinate with Schedule B and
Schedule C. Specify type and extent of system
required to suit project and local VAMC
practices/preferences.
6.7.8.7 ELECTRONIC ACCESS OR DOOR CONTROL:
Provide electronic access or door control//as specified in Schedule B// //[specify requirements]//. Access
control shall be provided for.
//Designated// //All// exterior doors// [_______]//
Pharmacy
Telecommunications head end and equipment rooms
Computer rooms ______ //clean and soiled utility //[__________]//
Door monitor switches shall be provided at [__________].
Part I: Basic Solicitation Requirements Page 133 of 169
Lessor __________ Gov't. __________