6.7.5.9 WET AND DAMP LOCATIONS:
Provide lighting fixtures UL-listed for wet locations in //cart washing,// showers and similar areas of high
humidity to insure proper fixture operation and longevity.
6.7.5.10 //PARKING GARAGES// //RESERVED//:
//
Provide suitable and cost efficient lighting for parking garages such as fluorescent, high intensity discharge
(HID) or high pressure sodium. Do not use low-pressure sodium. Consider safety and security for the
public in the lighting design. Installation of lighting fixtures should limit spill light and excessive glare to
adjacent private and public property.
The recommended foot-candle levels in Table 6.7.5 Illumination Levels of this manual, shall be the
minimum maintained values for interior parking facilities. Install additional lighting fixtures at the entrances
of parking garages to ease the adjustment from daylight to the low-level lighting inside the garage. Provide
a photoelectric sensor to switch these fixtures on during daylight hours and off at night.
//
6.7.5.11 EXTERIOR LIGHT SOURCES:
Utilize high-pressure sodium vapor light sources for exterior lighting.
Where a specific detail is to be highlighted (e.g., a Flag), use a metal halide source.
6.7.5.12 //OBSTRUCTION LIGHTING// //RESERVED//:
//
For cooling towers, buildings and smoke stacks, implement obstruction lighting per specifications upon
verification with the Federal Aviation Administration (F.A.A.), if such lighting is required. Refer to Advisory
Circulars 70/7460-1K, Obstruction Marking and Lighting. Advisory Circulars are available from FAA web
site at http://www.airweb.faa.gov/Regulatory_and_Guidance_Library/rgAdvisoryCircular.nsf . Hard copies
may obtained free of charge, with written requests only. Write or Fax to:
U.S. Department of Transportation
Subsequent Distribution Office
SVC-121-23 Ardmore East Business Center
3341Q 75th Ave
Landover, MD 20785
Publications Help Line:301-322-4961 (Phone); 301-386-5394 (Fax)
//
6.7.5.13 EXTERIOR FIXTURE CONTROL:
Use photoelectric sensors or astronomical time clocks as appropriate for each application.
Maintenance or security lighting for cooling towers shall be locally switched as necessary.
6.7.5.14.1 General:
All outdoor lighting shall comply with local outdoor lighting ordinances, if such exist.
Large parking lots shall be illuminated with pole-mounted fixtures. The maximum height of a pole shall be
40 ft.