Lighting circuits that are connected to the Life Safety Branch (i.e., egress lighting) shall not be switched.
Certain power circuits, which are identified in the Equipment Guide List, shall not be switched by the low-
voltage control scheme.
//
6.7.5.5 //DENTAL EXAM LIGHT SWITCHING// //RESERVED//:
//
Install a wall switch located away from the regular light switches at the door, preferably on a side wall
convenient to the dentist or assistant. Include a pilot light with the switch to indicate an active service.
//
6.7.5.6 EYE EXAMINATION ROOMS:
Provide fluorescent lighting fixtures with dimming ballasts and the following controls in each Eye Exam
Room in the Eye Clinic:
One 3-way switch at the strike side of the entrance door.
One 3-way dimmer switch on the side wall near the expected location of the projection screen.
One 4-way floor switch, foot operated, with approved rubber- insulated cable--approximately the
diagonal length of the room exposed on floor. Extend this switch from a recessed junction box
mounted 6 inches above the finished floor to clear the vinyl-base molding.
6.7.5.7 //HEMODIALYSIS EXAM// //RESERVED//:
//
In addition to a fluorescent fixture (two-level switch) over each patient lounge bed, provide a 250 W (watt)
quartz down light over both sides of the lounge bed. Control by a single dimmer control at the bed wall.
//
Editing Note: Refer to MCS SECTION 16515 MEDICAL
AND SURGICAL LIGHTING FIXTURES for detailed
requirements for fixture types. Type A is single head,
single arm; Type B is dual head / pivot arm fixture with
single point of suspension.
6.7.5.8 //SURGERY LIGHTS // //RESERVED//:
//
Surgical lights shall comply with VA Master Construction Specification 16515, Medical and Surgical
Lighting Fixtures.//
//Cystoscopic Room: Type A centered over the surgery table.//
//Minor Surgery Room: Type B centered over the surgery table. Note: If there is no Minor Surgery Room,
provide a Type A over each bed in the Life Support Unit.//
//Procedures Rooms (Cardiovascular Laboratory): Type A centered over the cardiac catheterization table.//
//Light Intensity Controls:
Type A
1
Type B
2//