JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
Editing Note: Edit to suit project requirements.
Coordinate with Schedule B.
6.7.8.8 DURESS ALARM OR EMERGENCY NOTIFICATION:
Provide the systems identified, required and specified in Schedule B.
Under no circumstance shall the Facility's telephone system be used to provide Duress Alarm Functions
although telephone SWP or UTP circuits may be used as long as there are enough spare pairs to satisfy
the telephone system installation and projected growth and each system does not interfere with the other.
6.7.9
TELEPHONE/DATA SYSTEMS:
Editing Note: edit to suit project requirements.
6.7.9.1 SYSTEM TYPES:
The systems may include any one or combination of the following:
Telephone Private Branch Exchange (PBX - identified Critical Service Operation) switch and PA
Systems (identified Public and Staff Safety and Emergency Operation)
A complete system(s) telecommunications distribution cable plant that is compatible with and fully
complements the Facility's existing Telecommunications Infrastructure Plant (TIP)
Dial dictation system for PBX function
Automated call director for PBX function
Radio paging interface for all Call Code One (aka Blue) functions
Data terminal, routing, modem and concentrating equipment
Wire Shielded Twisted Pair (STP) or Unshielded Twisted Pair (UTP) and Cable (fiber-optic and/or
coaxial) Distribution (inside and/or outside) System
6.7.9.2 CONDUITS AND BOXES:
All conduit runs shall contain no more than two 45-degree (or one 90-degree bend with access before and
after bend) bends (no LB/condulets) between pull and junction boxes, manholes or telecommunications
closets. Contact TCD-194D for technical approval for all conduit requirements.
Minimum radius of conduit bends shall be as follows:
Minimum Radius of Conduit Bends
CONDUIT SIZE
CONDUIT BENDS
(Inches)
RADIUS
(Inches)
3/4 minimum
9
1
11
1
14
1
17
2
21
2
25
3
31
3
36
4
45
All conduit bends shall be made so the internal conduit diameter is not reduced.
Conduit originating from telecommunications closets and pull boxes or wireways shall be in accordance
with the following criteria:
Part I: Basic Solicitation Requirements Page 134 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages