JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
Intercommunication Systems (identified as Public and Staff Safety Operation)
Master TV Antenna Equipment and Systems
Motion Intrusion Detection Systems (identified as Patient/Public/Staff Safety Operation)
PA Systems (identified as Public Safety Operation or Life Safety Operation when carrying Code Blue
or One calls)
Patient Annunciation Systems (identified as Emergency Operation)
Radio Entertainment Distribution Systems
Radio Paging System (identified as Public Safety Operation and upgraded to Life Safety when
interfaced to Code Blue or One calls)
Security Camera Systems (identified as Patient/Public/Staff Safety Operation)
Security Management (including stand alone) Systems (identified as Patient/Public/Staff Safety
Operation)
Two-Way Radio Systems (identified as Public Safety Operation for Security, Engineering and Medical
Functions)
6.7.6.1 GENERAL REQUIREMENTS:
6.7.6.1.1 Wires And Cables:
For all wire and cable installations follow the general guidelines outlined in VA Master Construction
Specifications (see Part VI of this solicitation).
6.7.6.1.2 Conduits And Interconnection Boxes:
For system conduits, junction boxes, routing, termination, risers, horizontal runs, sizing, etc., follow the
general guidelines VA Master Construction Specifications (see Part VI of this solicitation).
6.7.6.1.3 Open Wireways and Cable Trays:
Unless otherwise specified, install all system wiring and cabling in Occupational Health and Safety
Administration (OSHA) National Recognized Testing Laboratories (NTRL) approved telecommunications
open wireways or partitioned cable trays.
Wire and cable runs that are routed from open wireways or cable trays in interstitial spaces to the nearest
telecommunications closet, head end or Equipment Room or telecommunications outlet shall be enclosed
in conduit. However, the use of cable racks or ladders, installed from the telecommunications closet, is
preferred above the ceiling for station cable installation in non-critical areas as long as each location's
herein.
6.7.6.1.4 Telecommunications Ducts and/or Cellular Floors:
Provide these items, when required by system design.
Editing Note: edit to suit project requirements and
size.
6.7.6.2 //HEAD END (HE) EQUIPMENT ROOM// //RESERVED//:
//
6.7.6.2.1 General:
Provide a climatically controlled, secure and protected room in an area dictated by System Design. If other
than the Attic or Mechanical Penthouse is used, a separate 6 inches X 6 inches minimum cable chase
/duct or minimum conduit counts, as described herein, must be provided from the alternate location exiting
Part I: Basic Solicitation Requirements Page 130 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages