Conduit Sizing Criteria
NUMBER OF
CONDUIT SIZE(Inches)
OUTLETS*
1, 2
3/4
3, 4
1
5 and above
3
* Install conduit and outlet boxes for telecommunications outlets in solid or tiled walls, in freestanding
counter tops, walls containing fire stops or insulation and for telecarts and pay telephones.
Open Wireways Or Cable Trays: Provide as required by system design.
6.7.9.3 TELECOMMUNICATIONS OUTLETS:
Outlet boxes shall be the same minimum size as NEC standard quad (or dual duplex) electrical outlet
boxes.
Outlet boxes shall be equipped with quadruplex wall faceplates and four (4) category five RJ-45 jacks, and
contain enough space for one additional (1) fiber-optic and one (1) analog coax cable jacks (for a total of
six available jack positions) provided by the Contractor.
Unless otherwise specified, mounting heights for telecommunication outlets shall be:
Telecommunications Outlets Mounting Height
Pay station
4 ft. above finished floor
Wall outlet
4 ft. above finished floor
Desk outlet
1 ft. 6 inches above finished floor
Bedroom (telecart)
3 ft. 2 inches above finished floor
Special
As required
6.7.9.4 TERMINAL CABINETS:
May be used where the number of outlets served is minimal, the distance of the run is in excess of 300 ft.
from the otherwise nearest telecommunications closet and/or the cost of providing a telecommunication
closet, as described herein, is prohibitive. The use of terminal cabinets as a substitute for
telecommunications closets will not be approved.
Where required, each cabinet shall be: labeled, steel, not less than 18 gage steel code with doors and
concealed hinges attached by welding.
6.7.9.5 TELEPHONE EQUIPMENT ROOM:
6.7.9.5.1 Location:
The room shall be located within a cable distance of 100 ft. of the Console or Operator Room. It should be
located adjacent to the Main Computer Room and, if possible, as close as possible to an outside
telephone company cable entrance and not in a patient care area.
Avoid locations that are restricted by building components that limit expansion such as elevators, core
outside wall or fixed building walls. Accessibility for the delivery of large equipment shall be provided.
6.7.9.5.2 Power & Lighting:
Emergency Power - Provide an electrical panelboard in the Telephone Equipment Room and connect it to
the Facility's Critical Branch of the Emergency Power Distribution System. The panelboard shall be