8.3 CONDUITS AND BOXES
(A/E Note: Refer to VA Specification Section 16742 Infrastructure (Wire
and Cable) Telecommunications Equipment and Systems for additional
information)
8.3.1 GENERAL
(a) All conduit runs shall contain no more than two 45-degree (or one
90-degree bend with access before and after bend) bends (no
LB/condulets) between pull and junction boxes, manholes or
telecommunications closets. Contact TCD-194D for technical approval for
all conduit requirements.
(b) Minimum radius of conduit bends shall be as follows:
Table 8-1 Minimum Radius of Conduit Bends
CONDUIT SIZE
CONDUIT BENDS RADIUS
mm (Inches)
mm (Inches)
20 (3/4) (minimum)
225 (9)
25 (1)
275 (11)
32 (1 )
350 (14)
40 (1 )
425 (17)
50 (2)
525 (21)
65 (2 )
625 (25)
75 (3)
775 (31)
90 (3 )
900 (36)
100 (4)
1125 (45)
(c) All conduit bends shall be made so the internal conduit diameter is
not reduced.
(d) Conduit originating from telecommunications closets and pull boxes
or wireways shall be in accordance with the following criteria:
Table 8-2 Conduit Sizing Criteria
NUMBER OF OUTLETS*
CONDUIT SIZE mm (Inches)
1, 2
20 (3/4)
3, 4
32 (1 )
5 and above
75 (3)
* Install conduit and outlet boxes for telecommunications outlets in
solid or tiled walls, in freestanding counter tops, walls containing
fire stops or insulation and for telecarts and pay telephones.
(e) Install insulated bushings on conduit ends.
ELECTRICAL DESIGN MANUAL
8-3
TELEPHONE/DATA SYSTEMS