JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
SECTION 9: SAFETY, FIRE PROTECTION, AND ENVIRONMENTAL MANAGEMENT
9.1 GENERAL:
Space offered must have a current occupancy permit issued by the local jurisdiction.
Lessor shall inspect, test and maintain building systems, fire and life safety systems and equipment as
required by the more stringent of NFPA guidelines or local codes. Lessor shall submit documentation as
acceptable to the Contracting Officer of tests, report and maintenance logs.
As a minimum, systems and equipment for which inspections and reports include, but are not limited to,
those systems as enumerated in NFPA 99, other applicable NFPA guidelines, and the following:
Essential Electrical System
Gas and Vacuum Systems
Environmental Systems
Fire Doors and Shutters
Portable Fire Extinguishers
Automatic Fire Sprinkler Systems
Standpipe Systems
Fire Detection and Alarm Systems
9.2 CODE VIOLATIONS:
Equipment, services, or utilities furnished, and activities of other occupants, shall be free of safety, health,
and fire hazards. When hazards or code violations are detected, they must be promptly corrected at the
Lessor' expense. Where requirements conflict, the decision of the Contracting Officer shall be final.
s
9.3 SPECIAL ENVIRONMENTAL REQUIREMENTS:
All project planning and development shall comply with the National Environmental Policy Act of 1969.
As required, special building equipment to treat and exhaust the atmosphere toxic gases produced by the
agency program equipment will be provided. In addition, provide within all clinical laboratories and other
areas designated in the equipment drawings, exhaust air suitable to meet the special requirements and up
to 100 percent fresh air. All such installations shall comply with appropriate OSHA, EPA or related
regulations of the local community.
Part I: Basic Solicitation Requirements Page 167 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages