Design Illumination Level
Table 6.7.5
Area Description
Lighting Level (FC) *
Dedicated Chest Room
30; Incand. 0-10 f
Examination Room/Area
50
Film Library
50
Film Storage Undeveloped
10-30 b
Processing Area
50
Scrub Room
70
Special Procedures
Fluorescent
0-50 b
Incandescent
0-10 f
Ultrasound
50; Incand. 0-10 g
Viewing Room Common
20h
X-Ray Rooms
30; Incand. 0-10 f
Receiving And Cleaning
30; Benches,Tables,
etc., 70
Receiving And Issue Area
30
Receiving And Shipping Dock
20
Reception And Waiting
30
Shower
20
Specimen Toilet
30 e
Soiled Utility/SPD Cart
10
Stairways
20
Storerooms
Fine
50
Medium
20
Bulky
10
Stretcher And Wheelchair Storage
10
Stretcher Waiting Space
20
Switchgear
20
Telephone Equipment
20
Telephone Switchboard
50
Notes For Table 6.7.5
a.
Fluorescent lamps shall be of the color improved type, and shall essentially match the color
temperature of the surgical light(s).
b.
Vary illumination levels by conventional on off switches.
c.
Fluorescent lamps shall be of the deluxe color improved type.
d.
Control bed lighting individually.
e.
Footcandle value is for general illumination. Provide supplemental lighting for mirrors and close
inspections.
f.
Light dimming shall be in accordance with specific project requirements.
g.
Vary illumination levels by dimmer control devices.
h.
Lux (footcandle) value is for general illumination. Provide additional localized lighting as required.