5.2.10 EQUIPMENT PADS:
Locate the bulk oxygen storage pad, preferably, adjacent to the service area, easily accessible to trucks,
and well screened. The location shall comply with the local safety codes and NFPA Standard Nos. 50 and
99. Construct the oxygen storage and delivery vehicular parking area of reinforced concrete. Enclose the
storage area with a chain link fence and gate.
other equipment pads away from patient and visitor entries and outdoor activity areas, preferably adjacent
to service area. To prevent injury to patients and personnel, enclose pad area with chain link fencing.
Barriers and fencing shall comply with the requirements of the serving electric utility, where applicable.
Editing Note: Include following paragraphs if mobile
diagnostic equipment is in project program. Verify
available service voltage at site. Verify configurations
of receptacles and tele/data jacks with equipment to be
used. Verify design loading for equipment pad.
5.2.10.1 MOBILE MRI/CT SCANNER TRUCK PROVISIONS
Lessor shall provide the following provisions for mobile MRI/CT Scanner Truck:
Lessor shall furnish a dedicated five-wire //480 V, 3-phase wye connection with neutral and ground, 150
Amp circuit// //[____]// to supply power to mobile MRI/CT scanner trucks at the MRI pad shown on the site
plan. The safety disconnect switch shall have lock on provisions, which will allow the switch to be locked
in the "ON" position. The disconnect switch shall also have lock-off provisions. Provide safety disconnect
in electrical circuit, per code, on exterior of building for MRI/CT. Electrical feed shall terminate on exterior
of building at a //Russell Stoll #DF2504FRAB// //[____]// receptacle, in a weatherproof box. The bottom of
the receptacle shall be a minimum of 3 feet above grade. The disconnect switch, receptacle and
data/telephone jacks shall be mounted on concrete posts with strut framing adjacent to the MRI concrete
pad.
Lessor shall furnish a weatherproof box for data/telephone cable located adjacent to power receptacle.
Conduit shall extend from exterior data/telephone box to interior distribution system in the building. Install
//three (3) // //[___]// telephone lines and //one (1)// //[___]// data line. The telephone jacks and data line
jacks shall be marine telephone jacks.
Truck pad shall be Portland cement concrete //28// //[__]// feet wide by //62// //[__]// feet long Design
pavement section for loading in accordance with criteria in Paragraph 5.2.6.1. If reinforcement of concrete
is required, use only non-ferrous reinforcement materials. Variations in pad levelness shall not exceed
1/8-inch in 10'-0".
Provide the following plumbing provisions in two in-ground boxes adjacent to the truck pad. One in-ground
box shall be for water supply connections and one in-ground box shall be for sanitary wastewater
connection:
Provide a hose bib and backflow preventer, connected to a cold water supply line, for connection of a
inch hose.
Provide inch female connector and backflow preventer, connected to a cold water supply line, for
connection of a inch I.P.S. male threaded hose connector. Size line to provide 5 gallons per minute
at 45-60 psi. Provide an adjustable pressure regulator with gauge to insure that pressure does not
exceed 60 psi.
Provide 1-1/2 inch female threaded connector, connected to the sanitary wastewater drainage system,
for connection of a 1-1/2 inch male threaded hose connection.