[INSERT LOCATION OF FACILITY]
ventilation system must have a discharge above the roof level of the clinic building that is directed away
from the Clinic entrance or other possible clinic intakes. The smoking shelter shall be protected with an
automatic fire sprinkler system. Provide suitable lighting for smoking shelter, control with the other site
lighting.
5.4.3
CANOPIES AND COVERED WALKWAYS:
A non-combustible canopy is required at the walkway connecting the smoking shelter and the nearest
building entry//, //and to the screened enclosure// //[Insert other covered walks as necessary.]//. Design of
the //canopy// //canopies// shall be integrated with the building structure and architecture. Coordinate site
lighting with walkways. Provide fixtures below canopies and covered walks where necessary to maintain
Editing Note: Include if required by project program.
Indicate location and size on conceptual plans.
5.4.3.1 //SCREENED ENCLOSURE// //RESERVED//:
//The construction of the screened enclosure and its associated canopy shall be integrated with the design
of the building. //Provide two (2) each 42 inch blade fans with lights in the screened enclosure. Fans shall
have 5 blades. Lights on fans, and fans, shall be operated from wall switches within the screened
enclosure.// //Ceiling shall be 2 x 2 GWB lay-in panels //or moisture and abuse resistant AT// , rated for
exterior installation.// Screened enclosure shall have //concrete floor with broom finish// //[ ____ ]//.
//
Editing Note: Include if required by project program.
5.4.3.2 //GAZEBO// //RESERVED//:
//Provide a 12' X 12' octagonal gazebo near the front entrance of the clinic. Gazebo must be located a
minimum of 50 feet from any entrance to the clinic. Gazebo shall be painted, sealed, and include
benches, screening, screened door, and a copula. Gazebo shall be installed on a concrete pad
approximately 2 feet larger in dimension than the gazebo. An accessible sidewalk shall be installed from
the gazebo to the main entrance of the clinic. Gazebo shall be anchored to concrete pad per code
requirements. //Provide an overhead exterior grade 5-blade fan with 42-inch blades. //Gazebo shall be
fully sprinkled for fire protection. Provide lighting for gazebo. Lighting may be controlled with other site
lighting.
//
5.4.4
EXTERIOR ACTIVITY AREAS AND YARDS:
Provide //secured// exterior patio or yard areas for outdoor activities and dining.
//Dining patio of minimum //400// //[____]// square feet adjacent to Canteen dining room.//
//Outdoor areas shall be enclosed and secured by fences or walls. Design shall be approved by the
Contracting Officer. Gates and locking arrangements for the yards shall be provide for egress to comply
with NFPA 101.//
Outdoor areas shall be designed with a diversity of landscape and hardscape elements to create an
environment capable of accommodating a variety of activities.
5.5 UTILITIES:
5.5.1
WATER DISTRIBUTION SYSTEM:
Design and construct system to provide adequate water service for maximum domestic and fire protection
requirements.