JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
//Do not drain outside building sub-soil drain tile to an interior sump pump. If a pump is required, locate it
outside of the building. //
If required, design sewage pumping system to discharge at maximum sewage flow rate with largest pump
not operating. Connect pumping system to emergency power.
Wet well shall be large enough to allow an interval of at least 6 minutes between successive starts of same
pump motor throughout entire range of estimated flow rates. Include high water level alarm system in wet
well, and place warning bell in appropriate location.
//
5.5.5 GAS DISTRIBUTION SYSTEM:
Coordinate with gas company concerning housing and/or fencing for gas metering and regulating
equipment. Provide gas filter upstream of meter.
5.5.6
ELECTRICAL SERVICE:
Provide underground secondary-voltage electrical service from the serving electric utility. All requirements
of the electric utility shall be met, including location of service source, above-ground and underground
equipment locations, required easements and/or rights-of-access, above-ground equipment protection and
screening requirements, meter location and provisions for meter-reading access, co-location of service
conductors in common trench with other utility services, and all other applicable requirements of the
electric utility.
5.5.7
TELECOMMUNICATIONS SERVICES:
Provide underground telephone service from the serving telephone provider. Sufficient capacity shall be
provided at the Point of Presence (POP) for all telephone outlets identified in this SFO, plus 50% spare
capacity. Comply with all requirements of the telephone provider for cable installation, POP space and
security requirements, and POP equipment and access provisions.
Provide cable television service, subject to identical requirements as defined for telephone service.
5.6 EXTERIOR SIGNAGE:
Use Environmental Graphics Design Program Guide (Signage manual) for development of exterior
signage components. Calculations and structural drawings may also be required.
Lessor shall provide foundations as necessary and install VA furnished monument sign.
Editing Note: Edit following based on physical
security requirements and local preferences.
5.7
FENCING:
Ornamental //aluminum// //steel// fencing, 6 feet //[ __ ]// in height, shall be required adjacent to the
property line //around the perimeter of the total site// //as indicated on concept plans//. //[ Insert security or
other types of fencing per project requirements. ]// Furnish swing gates that will provide full accessibility at
all road entrances, with adjacent pedestrian swing gates minimum 36 inches clear width. All gates shall
have provisions for locking with a VA provided padlock. Include provisions for utility company and fire
department access as required by local authorities having jurisdiction. Fencing shall be //Jerith
Part I: Basic Solicitation Requirements Page 69 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages