temperature, as required for proper operation of the equipment. When
the equipment cannot be placed indoors, the primary switchgear shall be
located outdoors in a factory- assembled, weatherproof, tamperproof,
walk-in aisle enclosure. Equipment shall be located above the 100 year
flood plain.
primary power supply to mechanical equipment and for service to other
than Patient-care Buildings, use metal-enclosed fused switchgear
line-ups.
5.2.3 SECONDARY DISTRIBUTION
(a) Health Care, Research, Clinical and Ambulatory Care Facilities and
Essential Buildings with l000 kVA or Larger Demand Load: The total
building load (calculated demand kVA plus future growth) should be
served by multiple single-ended unit substations. A transformer shall
not supply more than half of the building load. The maximum transformer
size for 208Y/120 volt systems is to be 750kVA. The maximum transformer
size for 480Y/277 volt systems is to be 1500kVA. Provide integral,
interlocked primary selector switches (not loop feed) and load
interrupter switches with current limiting fuses for each transformer.
(1) The above requirement serves as a guide to the Engineer. Any
exceptions shall be submitted to the VA for review and written approval
prior to proceeding with the design.
(b) Other Health Care Facilities or Essential Buildings with Less than
l000 kVA Load: Use a single transformer with integral, interlocked
primary selector switches and load interrupter switches with current
limiting fuses.
(c) Quarters and Private Dwellings: Each dwelling shall have its own
kilowatt-hour meter, service disconnecting means and panelboard.
5.2.4 ELECTRICAL ROOMS
(a) Definition: An electrical room is an area located within a building
or structure which contains high-voltage transformers, primary
switchgear, secondary distribution equipment with related panelboards
or any combination of these.
(b) Construction: Any pipe or duct system foreign to the electrical
installation shall not enter or pass through an Electrical Room. The
Engineer shall ensure that foreign piping such as water pipes, steam
pipes, medical gas pipes, soil pipes, sanitary drains, storm drains,
A/C ducts and other unrelated systems are not installed in the
Electrical Room. Sprinkler piping serving only the Electrical Room
shall not be considered foreign to the electrical installation and not
pass thru the room and serve other areas. Electrical Rooms shall not be
located beneath toilets, showers, laboratories, kitchen or sinks.
(c) Existing Buildings Waterproofing: Where it is not possible to
comply with medical program requirements, a continuous metal pipe
sleeve or a membrane waterproof ceiling shall be provided below the
5-2
ELECTRICAL DESIGN MANUAL
ELECTRICAL POWER DISTRIBUTION