3. Master Antenna Television (Broadband) System: (MCS 16783, Master Antenna TV Equipment (MATV).)
Provide a complete VHF, UHF, and Master Antenna Television System. Provide a complete system to receive, amplify,
and distribute all local VHF / UHF signals to each antenna outlet, complete with all necessary antennas and masts, head-
end cabinet, amplifiers, splitters, lightning arrestor, ground, 75 ohm coaxial cable, screw-on type RF outlets, and other
devices required for a complete working system. Specific outlet location will be shown on approved equipment drawings.
Provide TV brackets at each MATV outlet. TV brackets shall be black, wall-mounted designer series for 13" to 27" TVs
as manufactured by Peerless Industries, or equal. Lessor to provide necessary in-wall backing for TV bracket.
$
Central Equipment
30
outlets
||content||
.00 each outlet.
30
TV brackets
||content||
.00 each bracket.
4. Motion Intrusion Detector (MID): (MCS 16727, Motion Intrusion Detector (MID).)
Provide a complete operational motion intrusion detection system. System shall include remote flush installed
annunciator panels in // Security Office// //and Central Reception Area// [________]. Unit shall include a light, buzzer,
silencing switch, and visual indication of location. The //warehouse// [_____] and Pharmacy shall have separate control
panels for entrance and exit and shall be connected to the main building system. An intrusion detection alarm system
shall detect entry into the room and broadcast a local alarm of sufficient volume to cause an intruder to abandon a
burglary attempt. Intrusion detector equipment that operates on the principle of narrow beam interception, door contacts,
microwave, or photoelectric eye is unacceptable. Intrusion detector system must have the following essential features:
(1) An internal, automatically charging DC standby power supply and a primary AC power operations.
(2) A remote keypad, for activation / deactivation of each zone, installed outside the room and adjacent to the room
entrance door frame.
(3) An automatic reset capability following an intrusion detection.
(4) A local alarm level of 80 dB (min) to 90 dB (max) within the configuration of the protected area.
(5) An integral capability for the attachment of wiring for remote alarm and intrusion indicator equipment (visual or
audio.)
(6) A low nuisance alarm susceptibility.
(7) Installation Notes:
(a) A locally sounding alarm should not be installed in a room that is close to special treatment areas
where a loud alarm could affect patients.
(b) Annunciators shall have the capability of identifying protected zones.
(8) System shall have the capability of transmitting alarms to an off-site alarm monitoring company.
$
Motion Intrusion System (MID) with:
6
Annunciation Panels / Central Equip.
62
||content||
.00 each detector.