JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
using a vertical discharge which shall extend well above the roof eddy zone. Coordinate cold-water make-
up connections and electrical power requirements for heat tracing with other trades for the wash down
cycle.//
//Provide a dedicated exhaust system to ventilate ETO sterilizer equipment, mechanical chase, floor
drains, deaeration units, and cylinder storage area. The exhaust system shall be separate from the general
exhaust system serving SPD area. ETO exhaust systems shall comply with state and local code
requirements.//
Editing Note: edit following paragraphs to suit project
requiremtens.
6.5.7
HVAC REQUIREMENTS FOR SPECIAL AREAS:
6.5.7.1 AMBULATORY CARE - EVALUATION AND EMERGENCY AREA:
Provide a dedicated HVAC system to serve the evaluation and emergency areas, including Minor
Operating Rooms (O.R.s).
MINOR O.R. (TRAUMA ROOM)
Discuss with the medical center the need for full operating room HVAC requirements. The HVAC systems
for the Minor O.R.s (Trauma Rooms) shall have the following features:
Constant volume air supply for O.R.s.
The remaining spaces of the emergency suite can have variable air volume supply
100 percent exhaust of the supply air
Individual room temperature control
Individual room humidity control is not required
Conventional overhead supply and exhaust air distribution.
Special air distribution, specified for the conventional (major) O.R.s, is not required
Maintain positive pressure in O.R.
6.5.7.2 AUDIOLOGY SOUND SUITES:
Provide a dedicated air terminal unit, (constant volume or variable air volume) with reheat coil, to serve the
examination and control rooms. Locate the room thermostat in the control room.
Supply at least 100 CFM in each room. With a variable air volume system, the reduction in air volume shall
be limited to 25 percent of the design airflow.
In the absence of the building HVAC supply air systems, investigate the possibility of using pre-fabricated,
engineered, ventilation system supplied by the sound suites manufacturers.
Editing Note: following paragraph applies to clinics
with a dedicated room for a CT scanner. Delete if
mobile unit will be used. See Paragraph 5.2.10.1
6.5.7.3 //CT SCANNER// //RESERVED//:
//The CT scanner has a function similar to the MRI unit, both being full body topography units. The CT is,
however, less sophisticated compared to the MRI.
HVAC equipment serving CT scanner area shall be on emergency power.