JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
Provide solenoid valve on cold water supply to the dental utility junction centers with control switch located
in the reception area.
6.6.2
DOMESTIC HOT WATER SYSTEMS:
Entire Building: Provide gas or electric storage type water heaters with the capacity of generating the flow
demand at 140 degrees F with each heater sized to supply 75% of demand. However, the heater
discharge temperature shall be set at 130 degrees F. Provide a water temperature alarm system on heater
discharge, or where water enters the piping system. Temperature limit stop of type T/P combination
temperature and pressure balancing valves shall be set at 105 degrees F at shower head. Use
recirculating system.
//Hydrotherapy Equipment: Provide simplex shell and steam coil booster heater to generate 140 degrees F
at point of use. //
Size the hot water supply and return lines by the heat loss method as outlined in the ASHRAE GUIDE
AND DATA BOOK, not to exceed 10 degrees F heat loss. Dead ends shall be limited to 20 feet.
Provide combination shut-off and balancing valves in the hot water return circulating lines.
6.6.3
DRINKING WATER EQUIPMENT:
Provide wall hung, self-contained, electric, wheelchair accessible, water coolers. Provide hi-low units in
areas where only one unit is provided.
6.6.4
SANITARY AND STORM DRAINAGE SYSTEM:
Design sanitary waste and vent systems in accordance with Plumbing Code. Design storm drainage from
roofs based on local storm duration in accordance with the Plumbing Code. Provide an adequate number
of sanitary and storm connections from the building.
//Kitchen waste shall be provided with a grease removal system.//
Provide chemical-resistant pipe for all waste and vent piping serving laboratory fixtures and photographic
developing equipment. Chemical drainage shall pass through an acid neutralizing tank before connecting
to the building sanitary drainage system. Install chemical-resistant vent pipe independently through the
roof.
6.6.5
INTERIOR FUEL GAS SYSTEM:
Design in accordance with NFPA 54.
Editing Note: Delete systems/components not
necessary for project program.
6.6.6
MEDICAL GAS AND VACUUM SYSTEMS:
Central Supply Systems: Design and construct medical gas and vacuum systems to deliver the following
pressures at the points of use:
Oxygen//, nitrous oxide// and medical air: 50 psi. In designing oxygen systems with adult ventilators,
size the piping system based on the instantaneous demand based on 7 scfm for each ventilator from
the outlet back to the source.
Part I: Basic Solicitation Requirements Page 104 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages