6.5.5.10 VENTILATING SYSTEMS:
Provide ventilation in the following areas where mechanical cooling may not be required but heating may
be.
OCCUPIED AREAS
Storage Facilities
Warehouses
UNOCCUPIED AREAS (WITHOUT HEAT PRODUCING EQUIPMENT)
Electrical Equipment Rooms
Mechanical Equipment Rooms
Telecommunications Closets
Editing Note: edit general and special exhaust to
delete areas/spaces not in program.
6.5.6
EXHAUST SYSTEMS:
6.5.6.1 GENERAL EXHAUST SYSTEMS:
The exhaust systems shall be conventional, low pressure, low velocity type serving toilets, day rooms,
janitor closets, //canopy type (A, B, and C) hoods,// soiled utility rooms, //dark rooms, // trash rooms, // etc.
The exhaust systems shall also include areas with 100 percent exhaust of the supply air, such as //surgical
suites, SPD,// //and laboratories (less special fume hoods)//.
In general, each supply air system shall have a corresponding general exhaust system to comply with
outdoor air requirements. The exhaust system may or may not be interlocked with supply air system. It
shall shut down when supply air system shuts down during unoccupied hours to conserve energy, except
exhaust fans shall continue to run when smoke is detected in the areas served by these fans.
6.5.6.2 SPECIAL EXHAUST SYSTEMS:
The special exhaust system includes dedicated exhaust systems for critical areas, such as laboratories.
Each dedicated exhaust system shall have its own exhaust fan and ductwork. It shall not be connected to
the general building exhaust system or another exhaust system.
To be in compliance with NFPA 90A, ducts connected to the special exhaust systems noted below are
hazardous and shall not be housed in the same shaft carrying environmental supply, return, and exhaust
ducts.
Laboratory Hood Exhaust Systems
ETO-Ethylene Oxide Sterilizers Exhaust Systems
Ortho/Prosthetic Laboratory Exhaust
//Battery Charging Rooms//
Ducts carrying make-up air connected to special exhaust systems may be installed in the same shaft with
environmental supply and/or return ducts.