All other duct systems such as return and exhaust, including branch ducts, shall be designed for a
maximum velocity of 1500 fpm for the duct mains and a maximum static pressure of 0.10 inch of water
gage per 100 ft, with the minimum duct area of 48 sq in, that is, 8 in x 6 in size.
Flexible duct connections at air terminal units, if used, shall be in accordance with VA standard detail
15840-30.
6.5.3
TEMPERATURE CONTROL CRITERIA:
Except for small HVAC systems or factory-packaged systems, the automatic control systems shall be
Direct Digital Controls (DDC) type with pneumatic, electric or electronic operators. Final selection of the
type of controls shall be confirmed with VA before proceeding with complete design of automatic
temperature control system.
The Lessor shall provide complete flow and control diagrams for air, water, glycol, and steam systems and
the sequence of operation for all HVAC systems and sub-systems. The diagrams shall show complete
operating description including starting, interlocks, part load operation, smoke control features, volumetric
controls, alarms, and emergency or power failure associated with operation of HVAC systems.
Temperature //and humidity// controls may be electronic //, electric (small jobs only),// or pneumatic //,
except that pneumatic or electronic control shall be required for the operating suites//. //Each humidistat
for an operating room shall directly control a terminal humidifier through high limit controller.//
Air compressors for pneumatic control systems shall be arranged to operate automatically with emergency
generator power in the event of utility power failure. Sizing of the air compressor is the responsibility of the
control system manufacturer based on a 1/3 on 2/3 off run time basis as outlined in the specification.
Control wiring and tubing shall be concealed. Use of wire mold will not be acceptable.
Mount room thermostats at 5 feet above the finished floor.
6.5.3.1 ROOM TEMPERATURE CONTROL:
All perimeter rooms shall have individual temperature control. As many as four small interior rooms of
similar function and load may be grouped into one zone. Laboratories and other spaces, in which the
supply air volume is based on special air requirements, shall also have individual temperature control.
Editing Note: Include following paragraph if size and
complexity of the HVAC systems justifies an EEC. At
a minimum, VA wants the HVAC monitoring software
installed on a VA computer, set up for VA system
parameters, and a modem for the computer to dial into
the system.
//6.5.3.2 ENGINEERING CONTROL CENTER (ECC):
Provide a complete Direct Digital Control (DDC) system with complete workstation consisting of a
computer, monitor, keyboard, and printer.//
6.5.4
SMOKE AND FIRE CONTROL:
The HVAC systems shall be designed to meet the requirements of the National Fire Protection Association
codes, NFPA 45, 72, 90A, 99, and 101, and the additional provisions outlined in this section. The Lessor
shall comply with local building codes that contain provisions in excess of these requirements.
The subdivision of the building spaces into smoke zones shall conform to NFPA 101.