JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
Administration, Offices, and assorted areas, such as:
Medical Records
Security Offices
Therapy Areas
Vending Areas
Volunteers
6.5.5.7 AIR HANDLING UNITS:
Provide draw-through type air handling units. All air-handling units comprised of coils, fans, filters, etc.
shall be of double wall construction. These units shall be factory-fabricated. Air handling units and similar
equipment shall be housed in a mechanical equipment room or in a mechanical penthouse building.
Penthouse type of fully weatherized roof top unites constructed in standard section of modules would be
acceptable in lieu of mechanical equipment rooms or mechanical penthouse.
6.5.5.8 AIR FILTERS:
Filter Efficiencies shall comply with test method specified by ASHRAE standard 52.1 and MERV values
based on ASHRAE standard 52.2.
Editing Note: edit to delete areas/spaces not in
program.
Filter Efficiencies (percent) for all Air systems
Pre-filters
After-filters
Area Served
Efficiency
MERV
Efficiency
MERV
Administrative areas, conference rooms, and lobbies
15
4
60
11
Dental Clinics
30
7
85
13
Dialysis Rooms
30
7
85
13
Emergency Care Units (Ambulatory Care}
30
7
85
13
Heat recovery Units (In exhaust air on upstream side of
30
7
-
_
the coil)
Laboratories, supply system
30
7
85
13
MRI, CT Scanners
30
7
85
13
Operating Rooms, and Trauma rooms
30
7
95
14
Medical Media
30
7
85
13
Make-up units for lab hood
30
7
-
_
Patient care such as examination, and treatment areas.
30
7
85
13
Pharmacy
30
7
85
13
Radiology
30
7
85
13
Special Procedure Rooms
30
7
85
13
SPD
30
7
85
13
Warehouses
30
7
-
_
Editing Note: in areas where little reheat is required,
edit text to provide reheat coils controlled by silicone
controlled rectifiers (SCR). In other areas, where gas
is available reheat shall be by hot water terminal
reheat.
6.5.5.9 VARIABLE AIR VOLUME (VAV) SYSTEMS:
VAV systems shall be single duct with hot water terminal reheat. The terminal units shall be pressure-
independent with factory set, but field adjustable, maximum and minimum air volumes settings.