Table 3-3 Medical Media Service - Expanded Core Areas
Air
Room
Room Name
Indoor Design
Air
Exhaust/
Pressure
Pressure
Conditions
Changes/Hr
Recirculation
Control
Air
Stat Camera
Special
Special
Special
Special
Special
Special
Special
Special
Special
Special
Illustration
Room (See
Notes (d)
and (e)
Special
Special
Special
Special
Special
Illustration
Prep. Room
(See Note
(c)
Special
Special
Special
Special
Special
Video
Editing CCTV
Control Room
(See Notes
(d) & (e)
Special
Special
Special
Special
Special
Computer
Imaging
System
Network
(CISN) (See
Notes (e) &
(f)
General
General
General
General
Special
Client
Review Room
(See Note
(g)
NOTES:
(a) The exhaust air can be taken through a prefabricated spray booth if
the scope of work includes such a system. Its location and capacity should
be coordinated with the architectural drawings. Assume approximately 5 Cu
M/Min (160 CFM) through each inlet hose connection for systems comprising
of 1 to 3 hoses.
(b) The exhaust air register 200 mm x 150 mm (8 inch x 6 inch) size with 4
Cu M/Min (150 CFM) capacity mounted at the counter height to remove air
from the work area. Coordinate location with the architectural drawings.
Note that all counters do not require exhaust air registers.
(c) Coordinate the exhaust requirements with the architectural drawings as
this area is supposed to be equipped with modified (without gas and vacuum
outlets) H7 hood. Provide a dedicated exhaust system for fume hoods.
(d) Room temperature shall not exceed 20 degrees C (68 degrees F).
HVAC DESIGN MANUAL
3-17
HVAC REQUIREMENTS FOR OCCUPIED AREAS