(e) Return Air System:
(1) The return air system shall be used if the return air volume is at
least 35 percent of the total supply air volume. When the return air
volume is below 35 percent of the total supply air volume, the air-
handling unit shall use 100 percent outdoor air and the total supply air
volume shall be fully exhausted outdoors.
(2) With a return air system, a return air fan shall be used to ensure
proper air balance, if deemed necessary. The air handling unit shall be
equipped with an economizer cycle for "free cooling" to conserve energy.
3.16.5.2 Cooling: The MMS air handling unit shall be served by a dedicated
air-cooled chiller to ensure the lower cooling temperatures required in
the space. Air-cooled chiller will also ensure availability of chilled
water whenever the central chilled water plant is not operating.
3.16.5.3 Heating: For heating, steam from the central boiler plant and/or
hot water generated by the steam to hot water heat exchangers shall be
used. For locations qualifying for perimeter heating, finned tube
radiation or overhead radiant ceiling panels shall be provided. The
perimeter heating shall be controlled by the room thermostat such that
cooling and heating do not come on line together. See Paragraph 2.7.2.
3.16.5.4 Exhaust System: A dedicated general exhaust
system shall be
provided to service the MMS. The exhaust air system shall be interlocked
with the air-handling unit.
Table 3-2 Medical Media Service - Core Areas
Air
Room
Air
Exhaust/
Room Name
Indoor
Pressure
Temperature
Changes/Hr
Recirculation
Design
Control
Air
Conditions
Darkroom
Special
Special
Special
Special
Special
Special
Special
Special
Special
Special
Darkroom
(Printing &
Enlarging)
Photo Finishing
Special
Special
Special
Special
Special
General
General
General
General
Special
Photo
Studio/A.V.
Recording (See
Notes (a) and
(b)
Photo
Special
Special
Special
Special
Special
Micrography
Camera Copy
Special
Special
Special
Special
Special
General
General
General
General
General
Audio Visual
Equip. Storage
/Checkout (See
Note (c)
HVAC DESIGN MANUAL
3-15
HVAC REQUIREMENTS FOR OCCUPIED AREAS