(c) The air distribution ductwork shall be constructed of either PVC or
3.17.2.2 COMPUTER COOLING UNITS: This unit is required for the High-field
system only. The specific requirements are:
(a) The air supply outlets shall be located at the floor level with the
air directed toward the cabinet inlets. The return air inlets shall be
located at the ceiling level, above the cabinets, and near equipment
(b) The physical location of the cooling unit should be coordinated with
the magnetic field line and should be away from the 10 guess (unit for
(c) The supply air entering the computer room shall be at 18 degrees C (65
degrees F) dry-bulb temperature and 60 percent RH maximum.
3.17.2.3 MRI COOLING UNITS: To cool the MRI and control equipment, a
dedicated, closed-loop water-cooling equipment shall be provided. The
equipment shall comprise of a dedicated air-cooled, chiller, circulating
pump and interconnecting piping. See Paragraph 2.12.9 for the dedicated
refrigeration unit. Other specific requirements are:
(a) The pH level, total solid content, total hardness, and alkalinity of
the circulating water shall be within the limits prescribed by the
equipment manufacturer.
(b) The limits of the inlet water temperature, pressure drop through the
equipment, and maximum inlet water pressure shall be in accordance with
the equipment manufacturer's recommendations.
(c) The water piping design shall meet the "Radio Frequency" requirements.
The piping laid in walls and chases shall be provided with clearly marked
and identified access doors for servicing valves and other piping
specialties.
(d) While the environmental and computer air handling units shall be
connected to the building central chilled water system, for back-up, the
capacity of the dedicated air-cooled water chiller shall also include the
cooling loads of the environmental air handling unit and computer room
cooling unit. The selection of the leaving chilled water temperature
shall, therefore, be such that the requirements of entering water
temperature to the water cooled equipment and the supply air temperatures
of the air cooling units are simultaneously satisfied.
3.17.2.4 ALARMS:
(a) Ambient Temperature Alarm: Provide a high temperature alarm local and
at the ECC, if available, for the temperature sensor. The sensor is to be
located near the top rear of the computer cabinets. The sensor will be
supplied by the MRI equipment manufacturer.
(b) Water Alarm: Provide water sensor alarms (local and the ECC, if
available) on the raised deck and under the raised flooring. It shall
close and sound the alarm upon detection of moisture water supply to the
equipment.
HVAC DESIGN MANUAL
3-19
HVAC REQUIREMENTS FOR OCCUPIED AREAS