Electrical:
Schematics*
DD**
CD***
Location and size of:
Primary distribution
switchgear/switchboard
Manholes
Location of smoke dampers and duct
Interconnection of electrical control
equipment with HVAC equipment
(see fire protection)
Smoke partitions and fire alarm zones
Fire alarm and signal riser diagrams
(see fire protection)
Calculations for emergency
Electrical details
Specifications
*
Submit, as a minimum, a single line layout for at a scale not less than
1:100 (1/8 inch). Submit a complete double line layout of areas of critical
importance, at a scale of 1:50 (1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated,
incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
scale floor plans, incorporating all revisions required by comments from the
design development phase.
Program Guide, PG-18-15, Volume C
28
May 2006