5. ELECTRICAL
a. Contact the electrical utility which will supply electrical power to the medical
center. Modify the previous submission documents to meet the utility company's
requirements. Submit a written summary of any conversations with the electrical
utility.
b. Submit a full set of electrical lighting, power and signal floor plans. Submit
proposed one-line and riser diagrams of the normal electrical power distribution
system and the emergency power system. Final equipment ratings may vary, but
locate all equipment and identify and size dimensionally for adequate capacity.
c. Provide preliminary load calculations.
d. Show location of primary distribution switchgear/switchboard,
other major items drawn to scale. Indicate the electrical equipment (panelboards,
transformers, etc.) to be installed in the proposed electrical closets based on the
preliminary riser.
e. Provide demolition plans to indicate the complete electrical work in all areas
to be renovated. If an entire wing or area is completely demolished, provide a
reference note to the architectural demolition drawings. Use Standard VA Symbols
for demolition and rewiring.
f. Submit two proposed lighting schemes for special areas such as: Main
Entrances/Lobbies, Public/Visitor Waiting Areas, Elevator Lobbies, Public/Visitor
Corridors, Canteen, Atrium & Skylights, Director/Administrator Office, Library,
Chapel, Day Room and Nurse Station. Vary each scheme in concept and materials
such as, fixture layout, fixture type, lamps, louvers, reflectors, etc.
g. Provide 1:100 (1/8 inch) scale floor plans which shall show typical power,
signal and lighting layouts for the following areas:
General Office
General Surgery Room
Secretarial Office
Major Surgery Room
Exam Room
Cysto Surgery Room
Nurse Station
Animal Surgery Room
Single Bed Patient Bedroom
Dental Hygiene Room
Two Bed Patient Bedroom
Dental Surgery Room
Four Bed Patient Bedroom
Clinical and Research Laboratories
Patient Toilet Room
Classroom
Waiting Room
Conference Room
Day Room
Dedicated Computer Rooms
Main Switchgear Vault
Interstitial Floor
Telephone Switchboard Room
Corridor
Pharmacy