Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Home Environment Clinic/Kitchen 36-B
Function:
This space is intended to allow the SCI patient to demonstrate independence prior to discharge.
Space Requirement:
160 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
N/A
Doors:
Not Required
Windows:
Not Required
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
150w
Equipment: 450w
People:
100w, sensible
130w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
-
Office of Facilities Management
193