Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Home Environment Clinic/Bathroom 36-D
Function:
This space is intended to allow the SCI patient to demonstrate independence prior to discharge.
Space Requirement:
75 NSF
Architectural:
Finish Code:
2-G
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
GWB/Ceramic Wainscot* 4'-0"
Ceiling:
Acoustical Tile; Plaster at Tub
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
14
Doors:
3'-0' x 7'-0" wood
Windows:
Not Required
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
35
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
Nurse Call
Ceiling Light
Office of Facilities Management
197