Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Function:
In this area medications are dispensed, cassette transfers are made and some IVs are prepared
providing immediate service to SCI Nursing Units.
This is an inpatient function and should be located in proximity to the nursing units.
Space Requirement:
390 NSF
Architectural:
Finish Code:
6-B
Floor Finish:
Carpet
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
See PG-18-3, Topic 1, Security.
Hardware:
157
Doors:
3'-8" x 7'-0" wood or metal security door with peephole.
Windows:
None
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
825
Equipment: 660w
People:
400w, sensible
520w, latent
Electrical:
Lighting Levels:
Gen. Illum: 70fc
Emergency Power:
-
Office of Facilities Management