Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
SCI Home Care Unit Interview Room 34
Function:
This space is intended to accommodate staff, patients, and their family in conferences prior to the
patient's discharge. This is located in the SCI Home Care Unit whose purpose is to provide for the needs
of SCI patients already discharged but not yet integrated into the community.
Space Requirement:
120 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
40
Slab Depression:
None
Special Construction:
-
Hardware:
23
Doors:
4'-0" x 7'-0" wood or metal
Windows:
Desirable, see PG-18-3, Topic 1, Codes and Standards; CS-31-1 & CD-35.
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
300w
Equipment: 300w
People:
150w, sensible
150w, latent
Electrical:
Lighting Levels:
High: 70fc
Low: 30fc
Incandescent Downlights on Dimmer
0-30fc
Emergency Power:
-
Office of Facilities Management
183