Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Unisex Patient Toilet 24
Function:
This space is intended to serve SCI Outpatients. A second toilet room (52 NSF) is required if a
Lithotrypsy/Cysto is included in the project.
Space Requirement:
52 NSF
Architectural:
Finish Code:
2-G
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
GWB/Ceramic Wainscot 4'-0"
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
14
Doors:
3'-6" x 7'-0", wood or metal, undercut
Windows:
None Required
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
Ceiling Light
Office of Facilities Management