Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
On-Call Bedroom 25-A
Function:
This space provides Living/Sleeping/Studying facilities for Physicians while on-call. It should be located
near the Intensive Rehab/Sustaining Care Beds.
This space is provided only when there are 100 or more SCI beds.
Space Requirement:
90 NSF
Architectural:
Finish Code:
6-A
Floor Finish:
Carpet
Base:
Vinyl
Wall Finish:
GWB/Vinyl Fabric Wallcover
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
19
Doors:
3'-0" x 7'-0" wood or metal
Windows:
None
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
150w
Equipment: 400w
People:
75w, sensible
75w, latent
Electrical:
Lighting Levels:
Gen. Illum: 10fc
Emergency Power:
Nurse Call
Office of Facilities Management
144