FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Special Procedures/Bronchoscopy Room
Design Standards
ARCHITECTURAL
ADP:
Yes
Ceiling:
Acoustical ceiling tile
Radio:
---
Ceiling Ht:
2890 mm (9'-6")
Telephone:
Yes
Wall Finish:
Vinyl wall covering
Intercom:
Yes
Wainscot:
---
Public Addr:
---
Base:
Resilient Base
Notes:
1.Junction box for CCTV
Floor Finish:
camera with conduit to
Slab Depr:
---
adjacent diagnostic room.
2.Junction box for poly
Notes:
1. 1200 mm (4'-0") wide door
somnograph cabling with
with 200 mm x 250 mm
conduit diagnostic room.
(8" x 10") tempered glass
3.Nurse call system.
view window.
SPECIAL EQUIPMENT
CONDITIONING
None
0
0
Dry Bulb Temp Cooling:
24
C (76 F)
0
0
25 C (78 F)
ELECTRICAL
Minimum % Outside Air:
---
General:
70 FC
Yes
Notes:
1.
600 mm x 1200 mm (2' x 4')
Noise Criteria:
NC-40
fixtures, acrylic prismatic
Steam:
---
lens, W/3-F32T8 lamps,
Relative Humidity/Cooling:
50%
3500k,CRI=75 (minimum)
Relative Humidity/Heating:
30%
2.
by dimmer.
Minimum Air Changes/Hr.:
8
Room Pressure:
Negative
POWER
AC Load-Equipment:
86 W/sm (8 W/sf)
General:
AC Load-Lighting:
22 W/sm (2 W/sf)
Emergency:
Number of People:
3
Notes:
1. Special receptacle for mobile
---
fluoroscopy unit. (Coordinate
with system supplier).
2. Receptacle for crash cart to
be on emergency power.
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-4