FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Exercise Room w/Patient Toilet & Shower
Design Standards
Toilet and Shower
CONDITIONING (cont'd)
ARCHITECTURAL
AC Load-Lighting:
toilet:27 W/sm (2.5W/sf)
Ceiling:
Plaster
exercise: 13W/sm (1.2W/sf)
Ceiling Ht:
(2700 mm) 9'-0"
Number of People: 6 for exercise;1 for toilet
Wall Finish:
Ceramic Tile
---
Wainscot:
---
Notes:
1.Heat gain from occupant
shall be higher than normal
Base:
Ceramic Tile
in exercise room.
Floor Finish:
Ceramic Tile
2.Minimum 10 Air Changes
Slab Depr:
75 mm (3") @ shower
per hour of supply air in
exercise room and
Notes:
minimum of 10 air changes
shower/ toilet room.
PLUMBING AND MEDICAL GAS
Cold Water:
Yes
Hot Water:
Yes
Laboratory Air:
---
Laboratory Vacuum:
---
Sanitary Drain:
Yes
Reagent Grade Water:
---
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
Yes
Notes:
---
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-3