FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Special Procedures/Bronchoscopy Room
Design Standards
CONDITIONING (cont'd)
Notes:
accomplished via low level
outlets.
2. Provide a special hood and
cleaning fumes if instrument
cleaning is done here rather
than in separate room.
3. If Bronchoscopy room is
used for tuberculosis patient
exams min. air changes per
hr. increases to 12 and
provide filtration as per TB
Criteria in HVAC Design
Manual for Hospital Projects.
PLUMBING AND MEDICAL GAS
Cold Water:
Yes
Hot Water:
Yes
Laboratory Air:
---
Laboratory Vacuum:
---
Sanitary Drain:
Yes
Reagent Grade Water:
---
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
Yes
Notes:
---
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-4