FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Blood Gas Analysis Room
Design Standards
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
22 0 C(72 0F)
Dry Bulb Temp Cooling:
Ceiling Ht:
2700 mm (9'-0")
22 0C (72 0F)
Wall Finish:
Paint
Minimum % Outside Air:
15%
Wainscot:
---
Yes
Base:
Resilient Base
Noise Criteria:
NC-40
Floor Finish:
Steam:
---
Slab Depr:
---
Relative Humidity/Cooling:
50%
Notes:
1. 900 mm (3'-0" ) wide door with
tempered glass view window.
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
6
SPECIAL EQUIPMENT
Room Pressure:
Negative
None
AC Load-Equipment:
129 W/sm (12 W/sf)
ELECTRICAL
AC Load-Lighting:
27 W/sm (2.5 W/sf)
Number of People:
4
General:
100 FC
---
Special:
---
Notes:
---
Notes:
1. 600 mm x 1200 mm
PLUMBING AND MEDICAL GAS
fluorescent light fixture,
acrylic prismatic lens,
Cold Water:
Yes
W/3-F32T8 lamps,
Hot Water:
Yes
3500k, CRI=75 (min.)
Laboratory Air:
---
Laboratory Vacuum:
---
POWER
Sanitary Drain:
Yes
General:
Reagent Grade Water:
---
Emergency:
---
Medical Air:
---
Notes:
---
Medical Vacuum:
---
Oxygen:
---
Notes:
1.Waste and vent piping
ADP: ADP needs direct interface of all ABG
material needs to be
equipment with DHCP, a printer, and
chemical resistant type.
a personal computer.
Radio:
---
Telephone:
Yes
Intercom:
---
Public Addr:
---
Notes:
---
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-2