FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Exercise Room w/Patient Toilet & Shower
Design Standards
ARCHITECTURAL
POWER
Ceiling:
Acoustical ceiling tile
General:
Ceiling Ht:
2700 mm (9'-0")
Emergency: 500W (crash craft receptacle)
Wall Finish:
Paint
Notes:
1. Junction boxes for elapsed
time clock and controls as
Wainscot:
---
required.
Base:
---
2. 220 VACv usually required
Floor Finish:
for treadmills.
Slab Depr:
75 mm (3") @ shower
Notes:
1. 1120 mm (3'-8" )wide door
with tempered glass view
window in exercise room.
ADP:
needs direct interface of all AGB
SPECIAL EQUIPMENT
equipment with DHCP, a printer, and a
workstation
None
Radio:
---
Telephone:
Yes
ELECTRICAL
Intercom:
Yes
General:
30 FC
Public Addr:
---
Notes:
1. Recessed lensed
incandescent shower
Notes:
---
light with 150W A-21 lamp,
U.L. listed for wet locations.
2. 600 mm x 1200 mm (2' x
CONDITIONING
light fixture, acrylic
0
0
Dry Bulb Temp Cooling:
24 C (76 F)
prismatic lens, W/2-F32T8
0
0
25 C (78 F)
lamps, 3500k, CRI=75
(min)U.L. listed for wet
Minimum % Outside Air:
15%
locations.
Yes
3. 600 mm x 1200 mm (2'x 4')
Noise Criteria:
NC 40
fixture, acrylic prismatic
Steam:
---
lens, W/2-F32T8 lamps,
3500 deg. K, CRI=75 (min.)
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr
10 (See Notes)
Room Pressure:
Negative
AC Load-Equipment:
32 W/sm (3 W/sf)
(Exercise Room)
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-3