25.
SUBMISSIONS
25.1
Submit calculations required under the Contract to include the
following systems and equipment:
Soil, Waste and Vent
Compressed Air
Storm Drainage
Oxygen
Pumps
Fuel Gas
Nitrous Oxide
Silver Recovery Piping
Vacuum
Hot Water Generation
Oral Evacuation
Domestic Water
Water Softening
Reagent Grade Water Piping
Water Dealkalizing
Therapeutic Pool(Filtering and
25.2
Recommendation regarding the necessity for installing insulation
on the domestic water and horizontal storm drainage piping for the
25.3
Water analysis, including pH, total hardness as CaCO3, total
dissolved solids, and alkalinity.
26.
PLUMBING FIXTURE SCHEDULES
conjunction with and superseding data found in the reference plumbing
code. Plumbing fixtures are described in Master Specification 15450,
PLUMBING FIXTURES.
26.1
Fixture Units:
P-NUMBER
DESCRIPTION
DRAIN
SUPPLY
CW
HW
TOTAL
101-105, 107
Water Closet, Flush Valve
4
5
-
5
110-113, 115
106
Water Closet, Tank Type
4
2.5
-
2.5
201-202
Urinal, Siphon Jet
4
4
-
4
302, 307
Bathtub
3
2
1
1.5
304
Bathtub, End Type
3
3
3
4
305
Perineal Bath (Sitz)
2
1.5
1.5
2
401-409, 411
Lavatory
1
.6
.6
.8
413-415
417-420
412
Washfountain, Semi-Circular
2
1.5
1.5
2
501-503
Service Sink
3
2.25
2.25
3
505
Clinic Service Sink
5
5
2.25
5
507
Plaster Sink
2
1.5
1.5
2
508-518
Sink, CRS
2
1.5
1.5
2
524, 528-531
519, 520
Surgeons Scrub Sink
2
1.5
1.5
2
24