B.
NUMBER OF OUTLETS, REQUIRING
PERCENT SIMULTANEOUS
f.
17 and over
50
2.
0.12 Standard L/min (0.25 SCFM)
a.
1 through 5
40
b.
6 through 10
30
c.
11 through 19
20
d.
20 and over
10
16.
SHOP COMPRESSED AIR SYSTEM
Provide simplex air compressor to serve equipment and a minimum of one
outlet on each wall in shop areas. Interior outlets shall be no farther
apart than 7500 mm (25 feet).
17.
THERAPEUTIC POOL EQUIPMENT
17.1
Water Treatment System:
A.
Pipes and Equipment: Use corrosion resistant piping and
equipment. Identify piping material on drawings.
B.
Filter: High rate [16 to 23 L/min per square meter (15 to 20
gallons per minute per square foot) of filter surface area]
sand type, pressure filter.
C.
Water Heater: Simplex shell and water coil heater shall heat
pool water capacity from 4 to 34 degrees c (40 to 94 degrees
F) in 24 hours with water entering the pool at not more than
49 degrees c (120 degrees F). Pool temperature shall be
maintained between 24 and 27 degrees C (75 and 80 degrees F)
for recreation purposes and between 30 and 34 degrees C (86
and 94 degrees F) for therapeutic purposes. Ambient air
temperature shall be 29 degrees C (84 degrees F).
D.
Disinfection: Feed calcium hypochlorite solution into pool
with influent water by adjustable pump to maintain a chlorine
E.
pH Balancing: pH shall be maintained between 7.2 and 7.8.
F.
Recirculating Pump: Recirculate entire contents of pool in 6
hours.
G.
Equipment Room: Locate pool equipment in enclosed space one
floor below pool room elevation. Entrance to pool equipment
room should be from pool apron and be lockable.
17.2
for cleaning.
18.
RISER DIAGRAMS
18.1
Provide diagrams for the following systems installed within the
buildings: Soil, waste and vent; reagent grade water; cold water;
hot water; hot water return; medical gas and vacuum; medical gas
19