6.26 EXTERIOR FIXTURE CONTROL
(a) Use photoelectric sensors or astronomical time clocks, as
appropriate, for each application.
locally switched, as necessary.
6.27.1 GENERAL
(a) Large parking lots shall be illuminated with pole-mounted fixtures.
The maximum height of a pole shall be 12.2 m (40 ft.).
(b) A combination of wall-mounted (mounted on exterior hospital wall)
and pole-mounted fixtures shall be used for illumination of small
parking lots. Wall-mounted fixtures shall be of the wall-pack type with
cut-off photo-metrics. Maximum pole height shall be 9.1 m (30 ft.).
(c) Renovations/Additions: Match existing pole/fixture styles.
(d) Lamp type shall be coordinated with the VA.
(e) Security and Landscape lighting is not addressed herein and may
affect the standards indicated. The site lighting shall be completely
coordinated lamp sources for general purpose, security and landscape
lighting shall be identical.
(f) Pole Protection: Preferred pole locations are islands and
landscaped areas beyond the reach of vehicle bumpers. When not
practical, extend concrete base 760 mm (30 inches) above finished
grade.
(g) Lighting Controls: Time clock/photocell combination
(h) Circuiting: For large lots, alternate circuiting to poles
6.27.2 LIGHTING LEVELS
(a) Minimize direct light onto windows
(b) Minimize illumination onto adjacent properties
(c) Maintained illuminances:
(1) Basic
ELECTRICAL DESIGN MANUAL
6-12
LIGHTING