(3) Chillers, chilled water circulating pumps, fans and controls for
animal research facilities
(4) HVAC equipment for Bone Marrow Transplant (BMT) areas
(5) HVAC equipment for Magnetic Resonance Imaging (MRI) Suites and
Computerized Topographic (CT) Scanners
(6) HVAC equipment serving emergency areas in outpatient clinics in
seismic and high risk hurricane areas
(7) Back-up HVAC equipment for Telephone Equipment Rooms and
Telecommunications Closets
(8) Computer Room HVAC Systems
(r) Hot Water Circulatory and Steam Condensate Return Pumps: Equipment,
controls, and light fixture and receptacle near the pumps
(s) Hot Water Generator: Equipment, controls, and light fixture and
receptacle near the generator
(t) Kitchen Area: Task illumination, minimum equipment to feed patients
during extended outage, frozen storage lockers and food refrigerators
(u) Laboratory Air Compressors and Vacuum Pumps: Equipment, controls,
and light fixture and receptacle near the compressors and pumps
(v) Mortuary Refrigerator or Cold Room: Refrigeration Equipment and
task illumination
(w) Radiology Suite: Task illumination, one automatic X-ray film
processor, and one X-ray unit
(x) Refrigerated Medical Storage: Refrigeration Equipment
(y) Sewage Pumps: Equipment, controls, and light fixture and receptacle
near the pumps
(z) Supply, Processing, and Distribution (SPD):
core, sterile storage, non-sterile storage, preparation, and
decontamination
(2) One ultrasonic cleaner
(3) One ethylene oxide gas sterilizer
(4) One steam sterilizer
(5) One washer sterilizer
4-7
ELECTRICAL DESIGN MANUAL
EMERGENCY ELECTRICAL POWER SYSTEMS