4.6.1.2 CRITICAL BRANCH
Shall supply power for task illumination, fixed equipment, selected
receptacles, and special power circuits serving the following areas and
functions related to patient care:
(a) Acute Nursing: Task illumination and selected receptacles
(b) Anesthetizing Locations: Task illumination, selected receptacles
and fixed equipment; task illumination includes battery back-up
(c) Angiographic Laboratories: Task illumination, selected receptacles
and selected power circuits
(d) Blood, Bone, Eye and Tissue Banks: Task illumination, selected
(e) Cardiac Catheterization Laboratories and Rooms: Task illumination,
isolated power units, and X-ray unit
(g) Emergency Room Treatment Areas and Life Support Rooms: Task
illumination and PBPUs
(h) General Patient Bedrooms: Night lights, an alcove or a lavatory
mirror light, one receptacle per bedwall, preferably in the PBPU, if
available and a bathroom light
(i) Hemodialysis Rooms: Task illumination and one receptacle for each
dialysis unit PBPU
(j) Human Physiology Labs: Task illumination, selected receptacles and
selected circuits
(l) Isolated Power Systems in special environments
(m) Medication Rooms and Medication Preparation Areas: Task
(n) Minor Operating Rooms: Task illumination, selected receptacles and
isolated power units (if provided)
(o) Nurse Call System: Equipment
(p) Nurses' Stations: Task illumination and selected receptacles
(q) Pharmacy Dispensing Area (including Satellite Pharmacies): Power
files, laminar flow hoods, refrigerators, electrostatic copier (i.e.,
Telautograph) for transmittal of physicians' orders, task illumination
and selected receptacles
(r) Psychiatric Bedrooms: Task illumination (ceiling only)
4-3
ELECTRICAL DESIGN MANUAL
EMERGENCY ELECTRICAL POWER SYSTEMS