26 February 1993
Environmental Laboratory
Design Standards
HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
Floor Area
240 NSF
Wall Finish
CMU (SC)
AC Load Lights
2.2 W/SF
Ceiling
PL
Wainscot
-
AC Load Equipment
2.0 W/SF
Ceiling Height
9'-0"
Base
ERF
Number of People
1
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
(0)
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
-
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
ENVIRONMENTAL CHAMBER
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
HVAC IN WORK AREA ONLY; SEE EQUIPMENT SPECIFICATIONS FOR
ENVIRONMENTAL CHAMBER
Lighting
Power
General
50 FC, 2.5 W/SF*
General
180 W
Special
A/R FOR CHAMBER
Special
**
Emergency
-
Emergency
-
Notes:
*WORK AREA
PLUMBING AND MEDICAL GASES
Sanitary Drain
-
Cold Water
-
**AIR COOLED CONDENSING UNIT: 30 A, 208 V, 3 PHASE
Acid Waste
-
Hot Water
-
CHAMBER: 60 A, 208 V, 3 PHASE
Silver Recovery
-
Reagent Water
-
CONTROL PANEL: 120 V
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-16