26 February 1993
Animal Treatment Room
Design Standards
HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
Floor Area
120 NSF
Wall Finish
CMU (SC)
AC Load Lights
6.6 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
12.9 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
2
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*EXAM LIGHT INCLUDED IN EQUIPMENT LOAD
Lighting
Power
General
100 FC, 5.0 W/SF*
General
900 W
Special
**
Special
500 W***
Emergency
-
Emergency
-
Notes:
*FLUOR LAMPS COLOR CORRECTED TO MATCH EXAM LIGHT
PLUMBING AND MEDICAL GASES
**EXAM LIGHT, (1) HEAD AT 120 W
Sanitary Drain
YES
Cold Water
YES
***RETRACTABLE CLG CORD
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
WALL MTD HAND FREE
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-3