26 February 1993
Quarantine Room
Equipment Guide List
SYMBOL
QTY
AI
DESCRIPTION
P-501
1
CC
SINK, SERVICE, REGULAR (H-08-1, MCS 15450; H-08-4, SD 4.1)
P-802
1
CC
HOSE BIBB, COMBINATION FAUCET, 24" OFF FLOOR, WALL MOUNTED, CONCEALED SUPPLY PIPES (H-08-1, MCS 15450; H-08-4, SD
4.2)
1
VV
HOSE REEL (IF ROOM IS OVER 120 NSF)
T-10
1
CC
RACK, MOP, WALL MOUNTED (H-08-1, MCS 10360; H-08-4, SD 64B & 66)
AR
CC
DRAIN, FLOOR (H-08-1, MCS 15400)
AR
CC
RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH WEATHERPROOF COVER PLATE (H-08-1, MCS 16140; H-08-3, CS 801-
3)
1
CC
RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH GROUND FAULT INTERRUPTER (H-08-1, MCS, 16140; H-08-3, CS 801-
3)
AR
VV
CAGES
-OR-
THE FOLLOWING EQUIPMENT ACCOMMODATES LARGE ANIMALS KEPT IN RUNS/PENS OR CAGES.
THE FOLLOWING ENCLOSURE FOR RUNS/PENS IS MODIFIABLE TO ACCOMMODATE VARIATIONS IN ANIMAL POPULATION (MUST
BE 24 - 30 SF).
FOR QUARANTINE OF SMALL ANIMALS, SEE EQUIPMENT FOR ANIMAL ROOM CUBICLE CONCEPT.
ALUMINUM OR STAINLESS STEEL ANIMAL ENCLOSURE COMPONENTS:
AR
VV
FRONT PANELS, WITH HORIZONTALLY SLIDING GATES, 4' WIDE X 7' HIGH
AR
VV
DIVIDER PANELS, LOWER PORTION SHEET AND UPPER PORTION ROD, WITH ADJUSTABLE LEGS, 6' LONG X 7' HIGH
AR
VV
END PANELS, ALL SHEET CONSTRUCTION, WITH ADJUSTABLE LEGS, 4' LONG X 7' HIGH
AR
VV
FLOORS, 3/4" WIDE FLOOR MEMBER SPACED, 3/4" APART, 2 (4' WIDE X 4' WIDE SECTIONS) REST ON ANGLES WELDED TO DIVIDER
PANELS, REMOVABLE
NOTE: FLOOR MEMBERS SHOULD BE HEAVY DUTY EXPANDED METAL, PLASTIC COATED, MOUNTED ON CROSS MEMBERS, 6"
ABOVE FLOOR.
AR
VV
FEEDERS, STAINLESS STEEL, FOR SLIDING GATES
AR
VV
RESTING BOARDS, 3/4" POLYPROPYLENE BOARD TRIMMED IN A SUITABLE MATERIAL TO PREVENT ANIMALS FROM CHEWING ON
THE BOARDS, I.E., ALUMINUM, APPROXIMATELY, 16" WIDE X 48" LONG, MOUNT IN REAR OF EACH RUN
AR
VV
AUTOMATIC WATER MANIFOLD, STAINLESS STEEL PIPE WITH ADJUSTABLE VALVE HEIGHT
VA Design Guide -- Veterinary Medical Unit