26 February 1993
Diagnostic Laboratory
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
120 NSF
Wall Finish
CMU (SC)
AC Load Lights
5.4 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
9.5 W/SF
Ceiling Height
9'-0"
Base
ERF
Number of People
2
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
NEGATIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
Lighting
Power
General
70 FC, 3.5 W/SF
General
STRIP MOLD 900 W
Special
-
Special
REFRIGERATOR
Emergency
-
Emergency
REFRIGERATOR
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
YES
Medical Vacuum
-
Laboratory Vacuum
YES
Oxygen
-
Fuel Gas
YES
Telephone
WALL MTD
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-2