ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
200 NSF (19.0 NSM)
Wall Finish
GYP .BOARD(SC)
AC Load Lights
3.5 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
5.0 W/SF
Base
Ceiling Height 9'-0" (2.75 METERS)
6" (152 mm) INTEGRAL
Number of People
5
Floor Load
-
COVE BASE
Noise Criteria
NC-40
Room Pressure
POSITIVE
WSF
Floor finish
Note:
Lead Lining
-
Dry Bulb Temp Cooling Range
78F (25C)
Refer to PG-18-1 and PG-18-6
72F (22C)
Minimum Air Changes per Hour
12(SA)
Minimum % Outside Air
100
YES
-
ELECTRICAL
Steam
-
Relative Humidity
50 %
Lighting
Power
Relative Humidity
30 %
General
100 FC, 3.0 W/SF
General
1800 WATTS*
Special
-
Special
-
-
Emergency
Emergency
-
*X-RAY ILLUMINATOR, (6) 300W
PLUMBING AND MEDICAL GASES
YES
YES
Cold Water
Medical Air
YES
YES
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
YES
Acid Waste
-
Nitrous Oxide
YES
TELECOMMUNICATIONS
Silver Recovery
-
-
Anesthesia Evac
YES
Patient Monitor
YES
Telephone
YES
YES
PART OF TELEPHONE
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
SPECIAL EQUIPMENT
Radio
-
None
Design Guide - Surgical Service
Design Standards
Guide Plate:
7-4b
200 NSF (19.0 NSM)
Date: August 2005