ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
100 NSF (9.3 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
1.5 W/SF
CT 4'-0" (1.22 METERS)
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
0.8 W/SF
8'-0" (2.66 METERS) Base
6" (152 mm) INTEGRAL
Ceiling Height
Number of People
1
Floor Load
-
COVE BASE
Noise Criteria
NC-40
WSF
Floor finish
Room Pressure
NEGATIVE
Note:
Lead Lining
-
Dry Bulb Temp Cooling Range
78F (25C)
Refer to PG-18-1 and PG-18-6
72F (22C)
Minimum Air Changes per Hour
10 (EA)
Minimum % Outside Air
-
YES
-
ELECTRICAL
Steam
-
Relative Humidity
50 %
Lighting
Power
Relative Humidity
30 %
General
40 FC, 1.5 W/SF
General
180 WATTS
Special
-
Special
-
ALL
Emergency
Emergency
-
PLUMBING AND MEDICAL GASES
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
YES
Sanitary Drain
Oxygen
-
-
Acid Waste
Nitrous Oxide
-
Silver Recovery
-
-
TELECOMMUNICATIONS
Anesthesia Evac
-
Patient Monitor
-
Telephone
-
-
-
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
SPECIAL EQUIPMENT
Radio
-
None
Design Guide - Surgical Service
Design Standards
Housekeeping Aids Closet
Guide Plate:
7-3b
(Serving Operating Rooms)
100 NSF (9.3 NSM)
Date: August 2005