ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
120 NSF (11.0 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
1.7 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
1.0 W/SF
Base
Ceiling Height 9'-0" (2.75 METERS)
6" (152 mm) INTEGRAL
Number of People
1
COVE BASE
Floor Load
-
Noise Criteria
NC-40
WSF
Room Pressure
NEGATIVE
Floor finish
Note:
Lead Lining
-
Dry Bulb Temp Cooling Range
78F (25C)
Refer to PG-18-1 and PG-18-6
72F (22C)
Minimum Air Changes per Hour
6
Minimum % Outside Air
100
ELECTRICAL
YES
-
Lighting
Power
Steam
-
Relative Humidity
50 %
General
40 FC, 1.5 W/SF
General
360 W
Relative Humidity
30 %
Special
-
Special
-
Emergency
Emergency
-
ALL
PLUMBING AND MEDICAL GASES
TELECOMMUNICATIONS
YES
-
Cold Water
Medical Air
Patient Monitor
-
Telephone
YES
YES
-
Hot Water
Medical Vacuum
-
-
Nurse Call
Intercom
Sanitary Drain
YES
Oxygen
-
Code One
-
Public Addr.
-
-
Acid Waste
Nitrous Oxide
-
-
CCTV
ADP
-
Silver Recovery
-
-
Radio
-
Anesthesia Evac
-
SPECIAL EQUIPMENT
None
Design Guide - Surgical Service
Design Standards
Soiled Holding/Disposal Room
Guide Plate:
7-5b
120 NSF (11.0 NSM)
Date: August 2005